Note for Maximum Number of Devices

Note for Maximum Number of Devices Version 1.10
Maximum Number of Network Slave products is 64 (in addition to the Master):
       The following equations also need to be satisfied:
 
       (1*a) + (2*b) + (3*c) + (4*d) ≦ 64
                 a: Number of slave products that occupy 1 station
                 b: Number of slave products that occupy 2 stations
                 c: Number of slave products that occupy 3 stations
                 d: Number of slave products that occupy 4 stations
 
        (16*A) + (54*B) + (88*C) ≦ 2304
                A:  Number of Remote I/O products
                B:  Number of Remote Device products
                C:  Number of Local Stations and Intelligent Device products
                                Local Station includes Standby Master station

TOP

Note for Maximum Number of Devices Version 2.0
Maximum Number of Network Slave products is 64 (in addition to the Master):
       The following equations also need to be satisfied:
 
       (a + a2 + a4 + a8) +
       (b + b2 + b4 + b8)*2 +
       (c + c2 + c4 + c8)*3 +
       (d + d2 + d4 + d8)*4 ≦ 64
 
       (a*32 + a2*32 + a4*64 + a8*128) +
       (b*64 + b2*96 + b4*192 + b8*384) +
       (c*96 + c2*160 + c4*320 + c8*640) +
       (d*128 + d2*224 + d4*448 + d8*896) ≦ 819
 
       (a*4 + a2*8 + a4*16 + a8*32) +
       (b*8 + b2*16 + b4*32 + b8*64) +
       (c*12 + c2*24 + c4*48 + c8*96) +
       (d*16 + d2*32 + d4*64 + d8*128) ≦ 2048
 
                a:   Number of units with 1 occupied station & 1 time setting
                b:   Number of units with 2 occupied stations & 1 time setting
                c:   Number of units with 3 occupied stations & 1 time setting
                d:   Number of units with 4 occupied stations & 1 time setting

                a2: Number of units with 1 occupied station & 2 times setting
                b2: Number of units with 2 occupied stations & 2 times setting
                c2: Number of units with 3 occupied stations & 2 times setting
                d2: Number of units with 4 occupied stations & 2 times setting

                a4: Number of units with 1 occupied station & 4 times setting
                b4: Number of units with 2 occupied stations & 4 times setting
                c4: Number of units with 3 occupied stations & 4 times setting
                d4: Number of units with 4 occupied stations & 4 times setting

                a8: Number of units with 1 occupied station & 8 times setting
                b8: Number of units with 2 occupied stations & 8 times setting
                c8: Number of units with 3 occupied stations & 8 times setting
                d8: Number of units with 4 occupied stations & 8 times setting
 
        (16*A) + (54*B) + (88*C) ≦  2304
                A:  Number of Remote I/O products
                B:  Number of Remote Device products
                C:  Number of Local Stations and Intelligent Device products
                                Local Station includes Standby Master station

TOP